PRODUCT DETAIL
DI-M9101 Intelligent Combination Heat Photoelectric Smoke Detector
DI-M9101 Intelligent Combination Heat Photoelectric Smoke Detector
Feature
☆ Address can be set in field
☆ Fault self-diagnostic
☆ Reed switch testing
☆ Built-in MCU can store 14 history messages
☆ Remote indicator output available
☆ Polling LED can be set to close
☆ 2 levels smoke sensitivities programmable, complies with UL268. Heat part complies with UL521
☆ UL listed
Technical Specifications
☆ Operating voltage: Loop 24VDC(16VDC~28VDC)
☆ Operating current:
Standby current: 0.8mA
Alarm current:≤1.8mA (without remote indicator)
☆ Setting of sensitivity and range:
Level 1: 1.23%~2.7% per ft
Level 2: 2.0%~3.89% per ft
☆ Action Temperature: 57.2℃
☆ Operating Environment:
Temperature: 0℃ ~+37.8℃
Relative Humidity: 95%, non-condensing
☆ Dimensions: Diameter: 100mm Height: 54.5mm (with base).